MBZ 300 * Smoke and heat extraction control panel for smoke and heat extraction drives with a total current consumption of 8 A to 72 A
- Modular design to allow flexible adaptation to project-specific requirements
- Convenient extension by clicking on other modules in a control unit
- Can be extended by alarm groups, ventilation groups and alarm lines as required
- Depiction of complex smoke and heat extraction scenarios
- Simple service and installation thanks to status display directly on the module
- Configuration software simplifies commissioning and configuration
- Wind direction dependent activation possible (SHEV according to EN 12101-2)
- Safety and reliability confirmed by VdS certification
Application Areas
- Small to large and networked smoke and heat extraction systems
- Control of electromotive 24 V drives for smoke and heat extraction in the event of a fire
- Control of a controlled natural ventilation
Technical data
MBZ 300 | |
Material | Sheeting |
Colour | grey RAL 7035 |
IP rating | IP30 |
Service temperature | -5 - 40 °C |
Operating voltage | 230 V AC |
Power consumption (max.) | 1440 W |
Connection cross-section / mains | 2.5 mm² |
Output voltage | 24 V DC +/-15% |
Residual ripple | 2 % |
Output current (max.) | 72 A |
Duty rating with maximum output current | 30 % |
Motor cable wire size | 10 mm² |
Battery capacity | 38 Ah |
Networking of several control units | connection with optional CAN Bus modules |
Signal outputs available | 1 status contact per CM/SM, 6 signal contacts per ERM for which parameters can be set |
Parameter setting of control units | via USB interface an PC software |
Standard conformity | EN 12101-10, ISO 21927-9 |
Approvals | VdS |